6Z63 Aluminium Aluminum heat-resistant Bus Tube

 Tip: Click on the image to enlarge
1.6Z63 Aluminium Aluminum heat-resistant Bus Tube
6Z63 Aluminium Aluminum high-strength heat-resistant Bus Tube can operate safely in 150°C—200°C environment, and its tensile strength can keep above 88% at room temperature under 250°C environment. This characteristic is suitable for ice melting device engineering and large-capacity substation engineering.
1) Implementation standard: GB/T27676-2011 aluminum and aluminum alloy bus tube pipe conductor or ASTM B 317M-07
2) Product Alloy: 6Z63(6063-Zr)
3) Product Temper: T6 
4) The product is hollow tubular structure with glossy surface, beautiful appearance and uniform size.
5)The outer diameter is from 60mm to 450mm.
6)The Wall thickness from 3mm to 15mm.
7) The length of a single bus tube pipe conductor can reach up to 15 meters.
 
2.The Chemical composition and Mechanical properties of 6Z63 Aluminium Aluminum heat-resistant Bus Tube
Alloy Chemical component(%)
Si Fe Cu Mn Mg Cr Zn   Ti Ni Other Al
Each Total  
6Z63
(6063-Zr)
0.2-
0.6
≤0.35 0.1-
0.2
≤0.1 0.45-
0.9
  ≤0.05 ≤0.15 Remain
 
Alloy Temper Mechanical properties
Tensile Strength(Mpa) Yield strength
(Mpa)
Elongation
(%)
standard value measured value standard value measured value standard value measured value
6Z63
(6063-Zr)
T6 ≥220 ≥240 ≥190 ≥205 ≥8 ≥9
 
Property / Alloy 6Z63(6063-Zr)
Density(g/cm³)
(20℃)
2.75
Melting point ℃ 640-668
Thermal conductivity,
(K /℃ x cm x s)
0.51
Electrical Conductivity IACS% 55
Poisson's Coefficient μ 0.317
20℃ Temperature coefficient of electrical  resistance
I/℃
0.003
20℃ Electrical Resistivity
β,Ω.m㎡/m
0.032
 
3.The external diameter allowable deviation and wall thickness allowable deviation of
6Z63 Aluminium Aluminum heat-resistant Bus Tube
3.1 The external diameter allowable deviation (unit: mm)
Nominal  external diameter >50~75 >75~120 >120~150 >150~200 >200~250
Normal level ± 0.23 0.30 0.40 0.60 0.80
High Precision level ± 0.15  0. 20 0.30 0.50 0.70
 
3.2 The Wall thickness allowable deviation (unit: mm)
Nominal Wall Thickness >3.0~4.0 >4.0~5.0 >5.0~8.0 >8.0~10 >10~15
Average wall thickness and
Nominal Wall Thickness  ±
Normal level 0.30 0.40 0.50 0.70 0.80
High Precision level 0.15 0.15 0.20 0.30 0.40
Any wall Thickness and
Nominal Wall Thickness  ±
Normal level 0.40 0.50 0.60 0.80 1.00
High Precision level 0.20 0.20 0.30 0.40 0.50
 
4.The main performance of 6Z63 Aluminium Aluminum heat-resistant Bus Tube as follows:
1) 6Z63 Aluminium Aluminum heat-resistant Bus Tube adopts hot-top casting seamless pipe tube etc a series of advanced technology, with smooth surface, high dimensional accuracy, high tensile strength, not easy to discharge and deformation;
2) 6Z63 Aluminium Aluminum heat-resistant Bus Tube has excellent machining, welding, conducting and heat resistance. The products were certified by the science and technology department and reached the international advanced level.
3) The convection heat dissipation condition is good, the temperature rise is low, the loss is small, the electrical conductivity is strong, the carrying capacity is big.
4) High heat resistance, which can increase the working temperature of the Bus Tube (working temperature is 150℃-200℃), and the conductor has higher mechanical strength at high temperature, so as to improve the safety and reliability of the transmission and transformation system.
5)The installation area is small, and the combined busbar is the 1/3 of the soft conductor installation area.
6)The corrosion resistance is strong,and it is not easy to ice coating, the ability to resist disasters is strong, and the service life is long.
7)Easy installation, beautiful appearance, safe, stable and reliable operation, convenient for maintenance.
 
5.The usage of 6Z63 Aluminium Aluminum heat-resistant Bus Tube:
6Z63 Aluminium Aluminum heat-resistant Bus Tube is mainly suitable for ice melting device engineering and large capacity substation project.
In addition,it is used as overcurrent conductor in power construction projects, such as conductor connection between power grid transmission conductor and transformer substation, jumper in transmission line, connection conductor in power equipment and high current DC ice melting device,It is a new conductor to replace the traditional rectangular, groove, bar-shaped bus and soft conductor.
It is one of the key equipment (materials) in power transmission and transformation system, and plays a vital role in the safe and reliable operation of power transmission and transformation system and power equipment.
 
6,Common tubular busbar, Liner tube & sealing ball size or sealing cover size.
Main Bus Pipe Tube Liner Bus Pipe Tube Sealing ball  or
Sealing cover
OD
(mm)
Wall Thickness
(mm)
OD
(mm)
Wall Thickness
(mm)
OD
(mm)
80 4 71 3 70
90 5 79 4 79
100 5 89 5 89
110 5 99 5 99
120 5 109 5 109
130 7 115 7 115
150 7 135 7 135
150 10 129 10 129
170 7 155 7 155
170 10 149 10 149
200 10 179 10 179
250 10 229 10 229